power
factor correction
................................................................................................................
high voltage PFC
Capacitors
Each capacitor consists of several series and parallel internally connected
elements. The container is made from mild or stainless steel suitable
for indoor and outdoor installation. Built-in discharge resistors reduce
the residual capacitor voltage to 50 V or less within 5 minutes of de-energisation.
The most commonly used capacitors are:-
• Single Phase two bushing type capacitor with both terminals
insulated.
• Single Phase one bushing type capacitor with one terminal insulated
and the other interconnected to the housing.
|
|
Single Phase Capacitor with 2 bushings |
Single Phase Capacitor with 1 bushing |
Single phase capacitors with or without internal fuses rated up to 21,600
Volts are available.
Three phase capacitors 2,400 V up to 4,800 V are available for rating
25 to 200 kVAr.
Capacitor Banks
Single phase and three phase capacitor banks are constructed with capacitors
connected in a series and parallel combination to give the required
output.
Capacitor Technologies manufacture various types of units to suit a
wide variety of installations and conditions.
Capacitor Bank Construction Types available are
• Totally enclosed
• Cubicle mounted
• Open rack mounted
Totally Enclosed capacitor banks are
suitable for power factor correction of motors where protection to the
capacitors is provided by the motor fuses. Alternatively totally enclosed
banks can be used for applications where external protection is available.
Open Rack type capacitor banks mounted
on galvanized steel frame or Cubicle mounted type can also be supplied,
ready for installing. The internal electrical connections are designed
in accordance with the bank being constructed.
Protection of Capacitor Banks
Shunt capacitors must be protected against internal faults resulting
in short circuiting and overload conditions. The protection can be categorised
into two types :
• Individual Protection
• Overall Protection
Individual Protection
Capacitors connected in star configuration may be provided with internal
fuses which disconnect the faulty element instantaneously avoiding case
rupture. As an alternative expulsion type fuses are used to protect
and isolate the capacitors at the first fault. Expulsion fuses can be
replaced where the capacitors have to be replaced after blowing internal
fuses.
Overall Protection
Special types of switchgear and protection systems suitable for switching
and protecting power capacitors.are used. The HV contactors and circuit
breakers used for capacitor bank switching must be re-strike free. Current
rating of the switching device should be carefully selected to take
care of the effect of harmonics in addition to the continuous overload
of capacitors.
Delta connected capacitor banks are commonly protected with external
current limiting HRC fuses.
Large three phase, high voltage capacitor banks are normally connected
in double star configuration. In order to prevent the over-stressing
of healthy capacitors due to successive fuse interruption in the circuit
of other capacitors, a current transformer is connected between the
two neutral points of the equally divided star groups. An overcurrent
relay with time delay may be required to be installed to protect against
an overload condition due to harmonics in the power system.
|
|
| Double Star Connected Capacitor Bank
|
Harmonic Blocking Reactors
Since capacitor impedance decreases with increase in frequency, the
presence of harmonics in the power system may cause an over voltage
and over current in the capacitor bank. The condition may also exist
that the capacitor bank starts resonating with the inductive elements
of the supply transformer or load.
Air core and iron core high voltage reactors, known as Blocking Reactors,
are used to reduce resonance in capacitive circuits.
Inrush Current Limiting Reactors
Capacitors draw a large inrush current during switching on. The peak
of this inrush curent may rise to a high value if a new stage is switched
in parallel with some capacitors already connected. In such cases, current
limiting reactors are required to limit the high inrush current transient
to an acceptable limit.
Rated Voltage
The voltage rating of capacitor banks are selected by first assessing
the effect of voltage rise at the capacitor terminal, due to the installation
of blocking reactors and the capacitors themselves. Consideration should
also be given to the normal supply variation in the supply system. Capacitor
units manufactured by Capacitor Technologies are designed to operate
with 10% continuous over voltage.
Rated Current
Capacitors normally have an over-current capacity equivalent to 1.3
times the rated current corresponding to rated voltage and frequency.
This over-current, due to harmonics, should be limited to this value
by means of series detuned harmonic blocking reactors.
|